Inspection
Inspection Details
Equipment ID
18314
18314
Inspection Date
3/18/2020
3/18/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Larry Taylor
Larry Taylor
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
fa6935ec-c58e-41c0-9811-0b91a00f99a5
fa6935ec-c58e-41c0-9811-0b91a00f99a5
Location
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO
Phone: (816) 889-4265
1 RIVERBOAT DR, N KANSAS CITY, MO
Phone: (816) 889-4265
Owner
Attn: Harrah's Casino- NKC
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and post a log in the machine room | 7/21/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | replace emergency light battery, it is dead | 4/1/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | replace the emergency light battery, it is dead | 8/17/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | do not store non-elevator related material in the machine room (toilet snake) | 7/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | replace the fire service phase 1 keyswitch collar, can not read markings on the collar | 5/31/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is to be updated every year | 5/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | smoke damper at the top of the hoistway is open, it should be closed and only open when smoke detector is activated or when the motor fails | 5/31/2022 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with bucket | 10/26/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | replace burnt out machine room light bulbs | 10/26/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | replace vic coupling in the machine room that is leaking all over the machine room floor | 10/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Recovery pump in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5 | 10/24/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Repair/replace vic coupling in the machine room that is leaking all over the floor | 10/24/2024 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 3.1 | No | No | Smoke damper at the top of the hoistway should be closed and only open when the hoistway smoke detectors are activated (2.1.4) | 10/24/2024 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.11.3.1.1(r) | Yes | No | Door restrictor has been disabled, repair and adjust the door restrictor | 11/4/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit, pile of rags should not be left in the pit | 10/24/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove scavenger pump from the pit | 7/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Adjust car door force to be 30 lbs or less | 12/4/2025 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Repair smoke damper at top of hoistway to function properly | 12/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | clean unexposed hoistway sills and door equipment | 7/18/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil from the pit floor | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Clean oil from the oil collection pan beneath the power unit | 7/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide updated permit in the cab or other specified location | 7/18/2025 |