Inspection
Inspection Details
Equipment ID
8980
8980
Inspection Date
3/18/2020
3/18/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Larry Taylor
Larry Taylor
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
11
11
External ID
c4de0f91-5db1-4a65-aff4-fc1c2df5064f
c4de0f91-5db1-4a65-aff4-fc1c2df5064f
Location
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO
Phone: (816) 889-4265
1 RIVERBOAT DR, N KANSAS CITY, MO
Phone: (816) 889-4265
Owner
Attn: Harrah's Casino- NKC
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Harrah's Casino- NKC
1 RIVERBOAT DR, N KANSAS CITY, MO 64116
Phone: (816) 889-7034
Email: rmurphy@harrahs.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | replace the emergency phone, it did not work and the phone line tested good | 3/18/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | repair elevator cab lights, they are not staying on | 1/10/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Perform monthly fire service test and post a log in the machine room | 7/21/2020 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.2c | No | No | repair duct work for car top a/c unit, ensure the a/c unit is in working order, glass back elevator exposed to direct sunlight | 7/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/14/2021 |
| A17.1-2016 : Elevators | 1.14 - Ventilation | 8.11.3.1.1(n) | No | No | make sure a/c unit on the car top is in working order | 5/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | the fire service phase 2 keyswitch collar markings cannot be read, replace collar | 5/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | in car stop keyswitch collar marking cannot be read, replace collar | 5/31/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | adjust nudging speed, doors will not close when keyed off of fire service phase 2 to return to the recall floor | 8/30/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is to be updated every year | 5/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean off car top, air conditioning unit that hasn't worked for years should be replaced with something that works. (glass back elevator) | 10/24/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Elevator would not return to recall floor when the phase 2 was turned off | 2/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top | 7/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Clean unexposed hoistway sills | 7/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide updated permit in the cab or other specified location | 7/18/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Provide updated maintenance task log | 7/18/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Machine room fire extinguisher inspection tag is expired, it was due for annual inspection in February 2026. | |
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | No | No | Jack head drain is clogged with lint and the oil is overflowing the head and running down the side of the jack. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean up oil on pit floor | |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | In case of fire use stairs signs missing on top and bottom landings |