Inspection
Inspection Details
Equipment ID
3508
3508
Inspection Date
3/12/2020
3/12/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
889be791-cddc-45c6-821b-94394e0f2ad0
889be791-cddc-45c6-821b-94394e0f2ad0
Location
Three Trails Elementary School
11801 E 32ND ST S, INDEPENDENCE, MO
Phone: (816) 521-5470
11801 E 32ND ST S, INDEPENDENCE, MO
Phone: (816) 521-5470
Owner
Attn: Geri Frink
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: Geri_frink@isdschools.org
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: Geri_frink@isdschools.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repair/replace broken tiles on the elevator cab floor, tripping hazzard | 3/19/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | the emergency phone did not work, the phone line was dead at the controller, provide working phone line to the elevator controller | 3/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | maintenance control program (MCP) documents shall be available in the machine room | 2/23/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | need to perform and log the monthly fire service test, keep log in the machine room | 2/23/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | replace burnt out pit light bulb | 2/23/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | reprogram elevator, fire service did not work at all | 1/7/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | adjust car door closing and opening, it slams open and close | 2/23/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | did not have Maintenance Control Program (MCP) documents in the machine room | 10/27/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not being filled out monthly | 10/27/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | repair the machine room door, the door has swelled and rusted so that it can only be opened with pry bars | 10/27/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | water in pit, pit equipment showing signs of rust, prevent the accumulation of ground water in the pit | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, provide working phone line | 8/6/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in pit, pit equipment showing signs of rust, prevent the accumulation of ground water | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide maintenance log for 2025 |