Inspection
Inspection Details
Equipment ID
6642
6642
Inspection Date
6/20/2018
6/20/2018
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Dennis Parker
Dennis Parker
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Moonrise Hotel
6177 Delmar Blvd, St. Louis, MO
Phone: (314) 727-8000
6177 Delmar Blvd, St. Louis, MO
Phone: (314) 727-8000
Owner
Moonrise Hotels, LLC
6504 Delmar Blvd, St. Louis, MO 63130
6504 Delmar Blvd, St. Louis, MO 63130
Billing
Attn: Moonrise Hotels, LLC
6504 Delmar Blvd, , MO 63130
6504 Delmar Blvd, , MO 63130
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.6.4.5 | Yes | Yes | Safeties set before the minimum required slide of 10 inches. Red tagged elevator. | 6/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | There is no lighting in machine space on top of hoistway. | 9/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | 1) Permanently installed electric lighting shall be provided in all machinery spaces, machine rooms, control spaces, and control rooms. | 9/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Permanently installed lighting shall be provided in all machine spaces, including top of hoistway. | 8/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance control program shall be provided on site. | 8/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current operating certificate shall be displayed in machine room. | 8/30/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of elevator on emergency power.. | 9/28/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of emergency generator selector switch. | 9/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | Provide hoistway door fire retainer, all floors. | 1/31/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | Yes | No | Provide testing of the elevator on emergency power. | 1/17/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 8.11.2.2.7 | Yes | No | Provide testing of the elevator emergency power selector switch. | 1/17/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 1/31/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | 1/31/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | During emergency power testing, car failed to recall to lobby. | 1/30/2024 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch in the lobby. | 1/30/2024 |