Inspection
Inspection Details
Equipment ID
16224
16224
Inspection Date
6/11/2018
6/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
Location
KC Chiefs Training Facility
One Arrowhead Dr, Kansas City, MO
Phone: (816) 918-5233
One Arrowhead Dr, Kansas City, MO
Phone: (816) 918-5233
Owner
Jackson County Sports Authority
#1 Arrowhead Drive, Kansas City, MO 64129
#1 Arrowhead Drive, Kansas City, MO 64129
Billing
Attn: Jackson County Sports Authority
#1 Arrowhead Drive, , MO 64129
#1 Arrowhead Drive, , MO 64129
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | Yes | No | 125% brake test not performed, did not have weights | 2/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.3.1 | Yes | No | 5 year governor test not performed | 2/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.29 - Car and counterweight safeties | 8.11.2.3.1 | Yes | Yes | 5 year safety slide not performed, did not have test weights | 2/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | perform monthly fire service test and post log in the machine room | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the copy of the state operating certificate in the machine room is to be updated every year | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | the monthly fire service test log is not being filled out | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | replace burnt out machine room light bulbs | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | No | No | the machine room fire extinguisher was last checked in 2019 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone went strait to busy signal | 2/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not connect to stadium security | 2/13/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not being filled out | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate posted in the machine room is to be updated annually, the one in the machine room is from 2015 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | do not store non elevator related material in the machine room | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate posted in the machine room expired in 2015, update with the current certificate when received from the state annually | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone was not answered, verify the phone line, verify the number dialed, reinspection required when fixed | 2/20/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating in the machine expired in 2015, update with a current operating certificate annually | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating in the machine expired in 2015, update with a current operating certificate annually | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Do not store non-Elevator related items in the elevator machine room |