Inspection
Inspection Details
Equipment ID
6784
6784
Inspection Date
5/8/2020
5/8/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Don McFadden, Jr.
Don McFadden, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
abf66591-0a5e-4a6a-8f8b-f86b857cf401
abf66591-0a5e-4a6a-8f8b-f86b857cf401
Location
Shell Building
1221 LOCUST ST, SAINT LOUIS, MO
Phone: (314) 621-1221
1221 LOCUST ST, SAINT LOUIS, MO
Phone: (314) 621-1221
Owner
Attn: Mike Jevicky
1221 Locust, LLC
417 Main St, Ste 303N, Little Rock, AR 72201
Phone: (501) 779-8557
Email: michael.jevicky@blueprinthospitality.com
1221 Locust, LLC
417 Main St, Ste 303N, Little Rock, AR 72201
Phone: (501) 779-8557
Email: michael.jevicky@blueprinthospitality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Existing cab emergency telephone does not work and shall be repaired and tested. | 5/30/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency phone shall work. | 5/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current state operating certificate. | 11/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit lighting shall be operational. | 11/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The machine room door shall be self-locking. | 11/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The machine room lighting shall not be less than 10 ftc at the floor of the machine room. | 11/17/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide annual testing of elevators on emergency power. | 2/23/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP. | 8/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Independent riser push button on door buck has broken halo ring,repair as needed | 8/14/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator appears to have emergency generator power, which needs to be scheduled and tested. Re-inspection required | 2/2/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | No | No | Emergency exit cover switch shall be operable. Repair/replace same. Re-inspection required | 7/28/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in elevator was not answered, phone not working. Re-inspection required | 2/2/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to provide testing of fire service to complete inspection. Re-inspection required | 2/2/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | Yes | No | Car top emergency exit not code compliant, make so. | 2/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Door restrictor out of adjustment, repair or replace as needed. | 2/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone works, but is requesting keypad entry, reprogram. | 2/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide Cat 1 testing of the elevator on emergency power. | 2/20/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide Cat 1 testing of the emergency power selector switch. | 2/20/2025 |