Inspection
Inspection Details
Equipment ID
19530
19530
Inspection Date
5/18/2020
5/18/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
358f3fc1-446d-474f-b183-48712e1c8cee
358f3fc1-446d-474f-b183-48712e1c8cee
Location
Fairground Park Place Apts
3644 NATURAL BRIDGE AVE, SAINT LOUIS, MO
Phone: (314) 534-7573
3644 NATURAL BRIDGE AVE, SAINT LOUIS, MO
Phone: (314) 534-7573
Owner
Attn: Fairground Park Place Apts
Fairground Park Place Apts
3644 Natural Bridge Ave, St. Louis, MO 63107
Phone: (314) 534-7573
Email: fairgrounds@pmapts.com
Fairground Park Place Apts
3644 Natural Bridge Ave, St. Louis, MO 63107
Phone: (314) 534-7573
Email: fairgrounds@pmapts.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. | 5/16/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 5/16/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 3/29/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car-top light shall be operational. | 3/29/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit light shall be operational. | 3/29/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | The governor rope and the suspension ropes shall be tagged as specified by CSR 40-5.065(L)1 | 3/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.11.2.1.1(b) - The in car stop switch shall be repaired or replaced. (The stop switch failed intermittently (open in the run position)). | 3/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.11.2.1.3(r) - The covers shall be properly installed on the car-top landing unit. | 3/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.11.2.1.3(w) - The broken pickup roller assembly at 2E shall be replaced. | 3/29/2024 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | All car call security lockouts shall be rendered inoperative on phase 2 fire service. This is the only working car in the building so the elevator was NOT red tagged. | 3/29/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/29/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The in car keyed stop switch shall be repaired or replaced. (The switch failed in a way that which made phase 2 fire service inoperable). | 7/8/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | The fire service visual and audible alerts in the car shall be functional. | 7/8/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | The fire service visual alert at the egress floor shall be functional. | 7/8/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water and oil shall not be allowed to accumulate on pit floors. (The pit has at least 1 foot of water in it). | 3/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 3/29/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Safe access to the machine room shall be provided. (The path to the machine room involves ascending a ladder in an unlighted space, and moving through the unlighted machine room of the service elevator that is not in service to get to the roof). | 3/29/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service is not working. Violation must be corrected within 14 days or elevator will be red tagged and locked out of service. | 11/4/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The complete annual and category 5 test that was originally scheduled for 9/12/24 is still due and was stopped due to fire service not working. | 11/4/2024 |