Inspection
Inspection Details
Equipment ID
16567
16567
Inspection Date
5/15/2020
5/15/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Ronnie Morris
Ronnie Morris
Relief Valve Pressure
350
350
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
bfd72b2d-216e-459c-aa74-76ac00dfc430
bfd72b2d-216e-459c-aa74-76ac00dfc430
Location
East Drive North Parking Garage
8015 BELLERIVE DR, SAINT LOUIS, MO
Phone: (314) 516-5311
8015 BELLERIVE DR, SAINT LOUIS, MO
Phone: (314) 516-5311
Owner
Attn: UMSL
UMSL
1 UNIVERSITY BLVD, SAINT LOUIS, MO 63121
Phone: (314) 516-5937
Email: starkeyjp@umsl.edu
UMSL
1 UNIVERSITY BLVD, SAINT LOUIS, MO 63121
Phone: (314) 516-5937
Email: starkeyjp@umsl.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car doesn't work - Recording says "wrong extension" can not complete call | 1/28/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Standby power fails to lower elevator and open doors when normal power is removed | 5/15/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load | 9/29/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load every 5 years. | 6/13/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The mud in the pit needs to be removed, and the pit needs to be dried. | 5/28/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light doesn't illuminate. | 5/28/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | All sump holes need to be covered | 5/28/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The battery lowering device fails to lower the car and open the doors when normal power is removed. | 5/28/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The mud in the pit needs to be removed, and the pit needs to be dried. | |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | All sump holes need to be covered | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The battery lowering device fails to lower the car and open the doors when normal power is removed. (Reinspect) |