Equipment ID
24721
24721
Inspection Date
5/21/2020
5/21/2020
Inspection Type
New Installation
New Installation
Inspector Name
David Hardin
David Hardin
Mechanic Name
John F Thrasher IV
John F Thrasher IV
Relief Valve Pressure
Slide
20
20
Governor Rope Pull
100/250
100/250
Door Closing Force
14
14
External ID
7b153391-4b90-4849-9fb9-19ab6648f382
7b153391-4b90-4849-9fb9-19ab6648f382
Location
SSM SLUH Hospital
1201 S Grand Blvd, Saint Louis, MO
Phone: (314) 602-1152
Email: flahm@alberici.com
1201 S Grand Blvd, Saint Louis, MO
Phone: (314) 602-1152
Email: flahm@alberici.com
Owner
Attn: Frank Lahm
Northstar Management Company
10820 Sunset Office Drive, St. Louis, MO 63144
Phone: (314) 602-1152
Email: flahm@alberici.com
Northstar Management Company
10820 Sunset Office Drive, St. Louis, MO 63144
Phone: (314) 602-1152
Email: flahm@alberici.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 6/24/2025 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. | 6/24/2025 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(d) On-Site Maintenance Records (Permanent Records) | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 6/24/2025 | ||
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | Generator testing has not yet been tested and shall be tested to complete the inspection | 7/6/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | The “Emergency Power” jewel failed to illuminate during emergency power testing, repair jewel to operate as required. | 6/24/2025 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | The “Emergency Power” jewel failed to illuminate during emergency power testing, repair jewel to operate as required. | 6/24/2025 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A written copy of the MCP shall be kept in the machine room for each unit | 6/24/2025 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room | 6/24/2025 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | The "Emergency Power" jewel failed to illuminate during emergency power testing, repair jewel to operate as required | 6/24/2025 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | The elevator cab suspended ceiling emergency exit panel is not removable without the use of special tools, needs repaired. | 6/24/2025 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Need to test Phase I & II fire service. Re-inspection required | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test elevator for operation on emergency power. Re-inspection required | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Need to clean trash from elevator pit | 6/24/2025 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | The “Emergency Power” jewel failed to illuminate during emergency power testing, repair jewel to operate as required. | 6/24/2025 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room | 6/24/2025 |