Inspection
Inspection Details
Equipment ID
17160
17160
Inspection Date
5/11/2020
5/11/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
Na
Na
Door Closing Force
17
17
External ID
a2cf8282-dda5-4308-934a-bf049c3a7950
a2cf8282-dda5-4308-934a-bf049c3a7950
Location
McGowan Lofts
1222 LUCAS AVE, SAINT LOUIS, MO
Phone: (314) 200-4680
1222 LUCAS AVE, SAINT LOUIS, MO
Phone: (314) 200-4680
Owner
Sean McGowan Condo Assoc
1314 WASHINGTON AVE STE 300, SAINT LOUIS, MO 63103-1919
1314 WASHINGTON AVE STE 300, SAINT LOUIS, MO 63103-1919
Billing
Attn: 1222 Lucas Lofts Condo Association
1709 WASHINGTON AVE STE 505, SAINT LOUIS, MO 63103-1729
1709 WASHINGTON AVE STE 505, SAINT LOUIS, MO 63103-1729
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 11/23/2020 |
| conversion | conversion | n/a | No | No | The electrical disconnect switch is missing a cover plate exposing the inner electrical panel. Reinstall the missing cover plate. | 11/23/2020 |
| conversion | conversion | n/a | No | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone for proper operation and passenger safety. | 11/23/2020 |
| A17.1-1996 : Elevators | 4.10 - Emergency doors blind hoistway | 1001.2(d)(10) | Yes | No | To fully comply with the 3rd floor to be an emergency door, the following shall be addressed. Interlock on hoistway door must be functional, and accessible on the landing side with a special key. Lobby side door shall be marked with "2" in high letters saying "danger, elevator hoistway". | 12/10/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/10/2020 |
| A17.1-1996 : Elevators | 4.10 - Emergency doors blind hoistway | 1001.2(d)(10) | Yes | No | To fully comply with the 3rd floor to be an emergency door, the following shall be addressed. Accessible on the landing side with a special key. Lobby side door shall be marked with "2" in high letters saying "danger, elevator hoistway". | 8/4/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | No lockable disconnect in machine room | 10/28/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 3/30/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate | 10/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency phone re-inspection in 15 days Friday (4/14/23). Car will be removed from service at this time if not repaired. This is the 4th year this violation has been submitted. | 4/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, have serviced or replaced | 10/28/2025 |
| A17.1-1996 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 100.6 | No | No | Bevel ledge in hoistway at first floor. | 10/28/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working, needs repaired/replaced | 10/28/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 10/28/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in machine room | 10/28/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 3/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in machine room | 3/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, have serviced or replaced | 3/11/2026 |
| A17.1-1996 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 100.6 | No | No | Bevel ledge in hoistway at first floor. | 3/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working, needs repaired/replaced | 3/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide means for pit light to be operational. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Means of two way communication are inoperable and shall be repaired. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | At this time the car door restrictor is failing to operate and shall be repaired or replaced. |