Inspection
Inspection Details
Equipment ID
136
136
Inspection Date
5/15/2020
5/15/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Douglas Dalton
Douglas Dalton
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
1cc0f696-8704-4c34-a71f-9213844852c3
1cc0f696-8704-4c34-a71f-9213844852c3
Location
AUM Hospitality
9600 NATURAL BRIDGE RD, SAINT LOUIS, MO
Phone: (314) 427-7600
9600 NATURAL BRIDGE RD, SAINT LOUIS, MO
Phone: (314) 427-7600
Owner
Attn: Airport Inn St Louis Airport
Airport Inn St Louis Airport
2401 E DIVISION ST, NATIONAL CITY, CA 91950
Phone: (000) 000-0000
Airport Inn St Louis Airport
2401 E DIVISION ST, NATIONAL CITY, CA 91950
Phone: (000) 000-0000
Billing
Attn: Airport Inn St Louis Airport
Airport Inn St Louis Airport
9600 NATURAL BRIDGE RD, SAINT LOUIS, MO 63134
Phone: (000) 000-0000
Email: mary.buckley@cpghotelsusa.com
Airport Inn St Louis Airport
9600 NATURAL BRIDGE RD, SAINT LOUIS, MO 63134
Phone: (000) 000-0000
Email: mary.buckley@cpghotelsusa.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Emergency phone shall work. | 5/22/2018 | |
| conversion | conversion | conversion - reinspect | x | Phone in cab still does not work | 11/6/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Current maintenance records to be kept in the machine room. | 4/29/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Pit shall be kept clean and dry. | 4/29/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A copy of the MCP shall be kept in the machine room for each elevator | 2/19/2026 | ||
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | OSV is not sealed. Must be Cat 5 tested. Re-inspection required | 2/19/2026 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone line is not working when on emergency power, Re-inspection required | 11/30/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Remove scavenger pump in elevator pit so oil loss can be monitored and logged in maintenance documents. | 2/19/2026 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | x | x | Phone in elevator cab does not work on battery backup, needs repair. Red tagged, Re-inspection required | 6/8/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | x | x | Alarm bell in elevator cab does not work, needs repair. Red tagged, Re-inspection required | 6/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Elevator cab emergency lights do not work. Re-inspection required | 6/8/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A copy of the MCP shall be kept in the machine room for each unit | 2/19/2026 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | x | Phone failed to operate would not dial out. | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | x | x | Alarm bell failed to operate | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No current operating certificate. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No MCP on-site | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | x | OSV due testing. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Remove scavanger pump from elevator pit, so oil loss can be monitored and logged in maintenance documents. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | A copy of the MCP shall be kept in the machine room for each unit. |