Inspection
Inspection Details
Equipment ID
2546
2546
Inspection Date
6/6/2018
6/6/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
280
280
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Maryland Ave Parking Garage
Maryland & Hospital, Columbia, MO
Phone: (573) 882-6463
Maryland & Hospital, Columbia, MO
Phone: (573) 882-6463
Owner
UMC-General Service
180 General Service Bldg, Columbia, MO 65211
180 General Service Bldg, Columbia, MO 65211
Billing
Attn: UMC- General Service
180 General Service Bldg, , MO 65211
180 General Service Bldg, , MO 65211
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Phase 1 Fire Service Recall Only, Door open button does not work on Phase 2 | 6/11/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 5/26/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate in machine room | 8/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove all non elevator related storage from machine room | 8/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Check control valve for leakback | 8/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | Provide a code data plate conforming to sec 8.9 | 8/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | bevel ledge at ground floor 100.6(4) | 10/17/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. Elevator hits the pit light and breaks it. Recommend moving the pit light, 5 foot candles to illuminate the pit. Recommend a 2 foot LED fixture which will fit tighter to the wall | 8/7/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 8/7/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide elevator machine room lights to work properly. |