Inspection
Inspection Details
Equipment ID
12401
12401
Inspection Date
8/9/2017
8/9/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
27/24
27/24
External ID
Location
City of St. Ann
10405 St. Charles Rock Rd, St. Ann, MO
Phone: (314) 428-8009
10405 St. Charles Rock Rd, St. Ann, MO
Phone: (314) 428-8009
Owner
St. Ann, City of
10405 St. Charles Rock Rd, St. Ann, MO 63074
10405 St. Charles Rock Rd, St. Ann, MO 63074
Billing
Attn: City of St. Ann
#1 Community Center Dr, , MO 63074
#1 Community Center Dr, , MO 63074
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Pit shall be kept dry. | 10/28/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has oil & water covering floor | 7/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 7/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pumps that do not record the amount of oil returned to the hydraulic tank shall not be installed in elevator pits. Install a maximum of a 5 gallon container in elevator pit to record oil loss | 7/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is due for full load test and tripping speed checked. On or before the next inspetion | 7/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. Re-inspection required | 8/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean oil from elevator pit | 7/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Rear car door restrictor does not work, needs repaired. Re-inspection required | 8/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pumps that do not record the amount of oil returned to the hydraulic tank shall not be installed in elevator pits. Install a maximum of a 5 gallon container in elevator pit to record oil loss | 7/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab not working Reinspection required | 6/27/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil from elevator pit | 7/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pumps that do not record the amount of oil returned to the hydraulic tank shall not be installed in elevator pits. Install a maximum of a 5 gallon container in elevator pit to record oil loss | 7/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in cab is not working. Re-inspection required | 6/27/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean oil from elevator pit | 7/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit has what appears to be water and/or oil in it. Pit shall be kept clean and dry | 7/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication device does not operate. Repair and reinspect | 7/31/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit has what appears to be water and/or oil in it. Pit shall be kept clean and dry | 7/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication phone does not operate. If not repaired in 14 days car will be red tagged and removed from service for consecutive years of violation | 7/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Yes | No | Scavenger pumps that do not record the amount of oil returned to the hydraulic tank shall not be installed in elevator pits. Install a maximum of a 5 gallon container in elevator pit to record oil loss | 7/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor on the rear doo is inoperable | 7/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has oil & water covering floor. Pit shall be kept clean and dry | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pumps that do not record the amount of oil returned to the hydraulic tank shall not be installed in elevator pits. Install a maximum of a 5 gallon container in elevator pit to record oil loss |