Inspection
Inspection Details
Equipment ID
3786
3786
Inspection Date
5/29/2020
5/29/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
6f9aac0d-008a-49a6-81a6-95ee1cda6860
6f9aac0d-008a-49a6-81a6-95ee1cda6860
Location
Hope Spring
3901 E 32ND ST, JOPLIN, MO
Phone: (417) 621-6341
3901 E 32ND ST, JOPLIN, MO
Phone: (417) 621-6341
Owner
Ozark Center- Joplin
3901 E 32ND ST, JOPLIN, MO 64804-3312
3901 E 32ND ST, JOPLIN, MO 64804-3312
Billing
Attn: Ozark Center- Joplin
PO BOX 2526, JOPLIN, MO 64803-2526
PO BOX 2526, JOPLIN, MO 64803-2526
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | pit needs to be dry and clean | 3/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 1.06 gtelephone does not work | 2/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone has no dial tone | 5/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light does not work | 5/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) . | 4/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Battery Lowering shall work. Repair. REINSPECTION REQUIRED =/> 5/30/22 | 2/10/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | Pit shall be kept dry. Standing Water on pit equipment. Clean pit and pit steel for reinspection of C-channels and pipe stands for possible replacement. REINSPECTION REQUIRED =/> 5/30/22 | 2/10/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Top emergency exit shall be secured properly. | 4/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | jack drain tubes shall be routed to a measurable container in the pit. Currently routed straight to tank. | 4/8/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current Stat operating Cert. 5.100(2) | 4/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Phone operable. Reinspection required in 14 days | 3/25/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Pit equipment must be cleaned to remove rust and re-painted. 8.6.4.7 | 4/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Must provide means to collect and Monitor jack packing gland oil usage. 8.6.5.5.2 | 4/8/2025 |