Inspection
Inspection Details
Equipment ID
11094
11094
Inspection Date
5/14/2020
5/14/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
faf73a2c-e70e-4baf-a7b1-82e57fc66a20
faf73a2c-e70e-4baf-a7b1-82e57fc66a20
Location
Grandview Tower
300 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 984-9700
300 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 984-9700
Owner
Grandview Apartment Homes LLC
300 S GRAND BLVD, SAINT LOUIS, MO 63103-2448
300 S GRAND BLVD, SAINT LOUIS, MO 63103-2448
Billing
Attn: Grandview Apartment Homes LLC % The Wellington Group
1715 DEER TRACKS TRL STE 220, SAINT LOUIS, MO 63131-1855
1715 DEER TRACKS TRL STE 220, SAINT LOUIS, MO 63131-1855
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide annual testing of elevator recall and power selector switch on standby power operation. | 2/17/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Provide cat 5 generator test | 9/14/2022 |
| A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | No | No | Provide testing of generator selector switch | |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Hoistway door missing bottom door guide, 1st floor left door | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Clean car top | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Provide phase 1 and 2 testing | 9/14/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work | 9/14/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 3/8/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be cleaned | |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Fire tabs shall be re-installed on 1st floor doors | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | Car top needs cleaning | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide annual testing of elevator recall & power selector switch on standby power operation. Reschedule emergency power test. Re-inspection required | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work when loss of normal power | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display Updated Missouri Operating Certificate in machine room |