Inspection
Inspection Details
Equipment ID
17341
17341
Inspection Date
5/19/2020
5/19/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
ed73df10-4fa5-419c-b37b-3caa9e4cde80
ed73df10-4fa5-419c-b37b-3caa9e4cde80
Location
Materdie Place Condos
660 MATERDIE LN # 664, FLORISSANT, MO
Phone: (314) 420-9422
660 MATERDIE LN # 664, FLORISSANT, MO
Phone: (314) 420-9422
Owner
Attn: UNK
Materdie North Condo Association
660 Materdie Ln, Unit 303, FLORISSANT, MO 63031
Phone: (000) 000-0000
Email: smstrizh@gmail.com
Materdie North Condo Association
660 Materdie Ln, Unit 303, FLORISSANT, MO 63031
Phone: (000) 000-0000
Email: smstrizh@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine Room not to be used for storage of non elevator related items. | 5/19/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | Post current State certificate in machine room 5.100(2) | 5/19/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Remove all non elevator storage from machine room | 5/19/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | Repair machine room ventilation (fan) | 5/19/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher is outdated as of 2011 | 5/19/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated certificate in machine room. | 5/19/2020 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV in pit is not sealed. Provide testing, tag and seal upon completion. 90 day compliance. | 2/24/2023 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean car top. | 11/19/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean pit. | 11/19/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Service or replace fire extinguisher in machine room. | 11/19/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Clean machine room. | 11/19/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light does not work. | 11/19/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV in pit is not sealed. Perform OSV test, tag and seal upon completion. 30 day compliance. The original violation was noted on 7/21 inspection report. | 11/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Service or replace fire extinguisher in elevator machine room. Noted on 7/21 report. | 11/19/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room shall be cleaned of dust and debris. Noted on 7/21 inspection report. | 11/19/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The weight test shall be performed, and the overspeed valve tested before the inspection is completed. | 11/19/2025 |