Inspection
Inspection Details
Equipment ID
15610
15610
Inspection Date
5/31/2018
5/31/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
22 lbf
22 lbf
External ID
Location
Value Place Hotel
888 Arnold Commons, Arnold, MO
Phone: (636) 287-6441
888 Arnold Commons, Arnold, MO
Phone: (636) 287-6441
Owner
Value Place Hotel
888 Arnold Commons Dr., Arnold, MO 63010
888 Arnold Commons Dr., Arnold, MO 63010
Billing
Attn: Value Place Hotel
888 arnold Commons Dr., , MO 63010
888 arnold Commons Dr., , MO 63010
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not call the correct elevator maintenance company. | 4/21/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The car top shall be cleaned. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | The pit shall be kept clean. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.16 - Rated load, platform area, and data plate | 8.11.2.1.1(p) | No | No | The capacity sign in the cab is illegible. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | No | No | The heat detector in the machine room shall not affect the operation of the elevator or the shunt trip since there is not a sprinkler head present. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Label the main electrical disconnect with the source panel and breaker. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | Upper and lower hoistway access switches shall be momentary/spring return. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | Upper and lower hoistway access does not stop. Adjust for code compliant stop. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | The heat detector in the machine room shall not affect the operation of the elevator or the shunt trip since there is not a sprinkler head present. - Re-Inspection Required | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 9/13/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Pit light shall work. | 9/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform OSV test on or before next annual inspection. | 9/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | 6/23/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 6/23/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not work, appears to not have live phone line. Re-inspection required | 6/28/2022 |