Inspection
Inspection Details
Equipment ID
10511
10511
Inspection Date
5/21/2020
5/21/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
612fe50a-41cf-41ba-9a0f-8ccd66650fa1
612fe50a-41cf-41ba-9a0f-8ccd66650fa1
Location
Bank of America- St. Louis
4625 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 655-6000
4625 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 655-6000
Owner
Attn: UNK
TCG BOA MO Holdings, LLC
425 5th Ave 30th Floor, New York, NY 10018
Phone: (314) 655-6000
TCG BOA MO Holdings, LLC
425 5th Ave 30th Floor, New York, NY 10018
Phone: (314) 655-6000
Billing
Attn: Balke Brown Associates
CBRE
1 North Bretwood Blvd Ste 540, Clayton, MO 63105
Phone: (314) 655-6000
CBRE
1 North Bretwood Blvd Ste 540, Clayton, MO 63105
Phone: (314) 655-6000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phase II not working | 2/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Drive machine brake pins not freely moving, perform maintenance. | 10/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide callback log and maintenance control program. | 10/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | No | No | Provide braille/tactile plates on all jambs, as needed. | 10/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 8.11.2.1.3(k) | No | No | Provide corrected crosshead data plate. | 10/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.3.2 | Yes | No | Seal governor. Was never done from final acceptance. | 10/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone rings to previous contractor. Reprogram. | 10/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 10/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | Yes | No | Drive machine brake pins not freely moving, perform maintenance as needed. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide missing maintenance: Call Back Log | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide maintenance control program. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current elevator operating certificate in machine room. | 11/4/2020 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | Provide braille/tactile plates on all jambs, as needed. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | No | No | Provide correct crosshead data plate. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.7.1.8 | No | No | Provide corrected data plate on governor in machine room. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.3.2 | Yes | No | Seal governor. Was not done on final acceptance. | 10/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean and dry. | 4/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be answered by proper personnel 24x7. | 4/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 4/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the elevator machine room | 11/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Current fire extinguisher located in the elevator machine room is expired. |