Inspection
Inspection Details
Equipment ID
10876
10876
Inspection Date
6/2/2020
6/2/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
240
240
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
023f2ed7-a94f-4794-9c7f-5515ddbc58e8
023f2ed7-a94f-4794-9c7f-5515ddbc58e8
Location
FP-San Remo
900 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Phone: (314) 645-6033
900 N KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Phone: (314) 645-6033
Owner
Attn: UNK
Robert Wood Realty
625 N EUCLID AVE, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: cdunn@fox-grove.com
Robert Wood Realty
625 N EUCLID AVE, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: cdunn@fox-grove.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone not working | 9/13/2018 |
| conversion | conversion | n/a | No | No | Pit needs to be clean and dry the pit has 6 inches of water | 7/26/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from the elevator pit. | 7/26/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace missing braille tags. | 7/26/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. | 9/24/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 1/11/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room floor is covered in sewage, the sewage line shall be repaired and the machine room floor cleaned thoroughly. | 1/11/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit shall be clean of all water and oil and debris. | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Elevator pit shall have a 5 gallon pit bucket to keep record of amount of oil loss | 9/26/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water and oil shall not be allowed to accumulate on pit floor. | 9/26/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The pit structure appear to be severely rusted. This couldn't be investigated because of standing water in the pit. The water shall be removed, and the pit structures inspected to determine structural integrity. If any are found to be unsound, they shall be replaced. | 9/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machinery and control spaces shall be kept free of water, dirt, rubbish, oil, and grease. The waste oil being stored in the machine room shall be removed. | 9/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/26/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation, and the date shall be available on site. | 9/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 9/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car telephone shall be operational. The phone was tested and found to be unresponsive both on main and auxiliary power. This shall be corrected and re-inspected within 14 days. | 9/26/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall be operational. | 9/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. It was closed and unlocked when we arrived for the inspection. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. A suitable container shall be provided in the pit. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The oil leak(s) in the machine room pump unit shall be identified and corrected. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The top of car shall be kept clean. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. A suitable container shall be provided in the pit. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | The oil leak(s) in the machine room pump unit shall be identified and corrected. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The pit structure appear to be severely rusted. This couldn't be investigated because of standing water in the pit. The water shall be removed, and the pit structures inspected to determine structural integrity. If any are found to be unsound, they shall be replaced. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation, and the date shall be available on site. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |