Inspection
Inspection Details
Equipment ID
10270
10270
Inspection Date
5/14/2020
5/14/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
3d9e9abf-df16-49ef-a655-158cd4d97275
3d9e9abf-df16-49ef-a655-158cd4d97275
Location
MO Baptist Medical Center
3015 N NEW BALLAS RD, ST. LOUIS, MO
Phone: (314) 996-5000
3015 N NEW BALLAS RD, ST. LOUIS, MO
Phone: (314) 996-5000
Owner
Attn: MO Baptist Medical
MO Baptist Medical Center
3015 N BALLAS RD, SAINT LOUIS, MO 63131
Phone: (000) 000-0000
Email: gerald.erickson@bjc.org
MO Baptist Medical Center
3015 N BALLAS RD, SAINT LOUIS, MO 63131
Phone: (000) 000-0000
Email: gerald.erickson@bjc.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light shall work. | 3/17/2022 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency alarm bell does not work when 110V circuit removed and shall be made operational. | 5/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Clean the car top. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Provide numbering on car top. | 3/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Clean the pit. | 3/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.7.1.8 | No | No | Provide a code data plate on the controller. | 3/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | 8.11.3.1.3 - Observed hoist rope shackle jamb nut (one at counterweight side) not secured. Secure the jamb nut. | 3/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Provide working audible indicator on Phase 1 recall. | 5/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency light shall work. (Violation not cleared from previous annual inspection) | 3/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell does not work when 110v circuit removed, and shall be made operational. (Violation not cleared from previous annual inspection) | 5/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | Provide working audible indicator on Phase 1 recall. | 7/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | A code data plate meeting the requirements of A17.1 2005 - 8.9 shall be installed on all controllers in this elevator group. | 3/17/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Elevator returns to the wrong floor on Phase 1 fire recall. Violation corrected on 9/21/2020 and scheduled for re-inspection on 10/5/2020. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 3/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | The emergency/standby power operation of the elevator shall be tested. | 12/29/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested. | 12/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit lighting shall be operational. | 3/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 9/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 9/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell shall work with and without main 120v power. | 9/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Current test tags shall be installed on governor, safeties (releasing carriers), buffers, etc. | 9/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log, and fire service log recorded monthly. | 9/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no operating certificate in the machine room. | 9/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean and free of dirt, oil, and debris. Remove excess debris. | 9/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Fire service shall be tested. | 9/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator | 9/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Fire service shall be tested. (2nd Notice) | 5/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Emergency power shall be tested. (2nd Notice) | 5/16/2026 |