Inspection
Inspection Details
Equipment ID
18999
18999
Inspection Date
6/18/2018
6/18/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
Location
Iatan Station
20256 Hwy 45 North, Weston, MO
Phone: (816) 386-2047
20256 Hwy 45 North, Weston, MO
Phone: (816) 386-2047
Owner
KC Power & Light
1201 Walnut, Kansas City, MO 64141-9679
1201 Walnut, Kansas City, MO 64141-9679
Billing
Attn: Iatan Power Plant
20250 Hwy 45 N, , MO 64098-8902
20250 Hwy 45 N, , MO 64098-8902
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Alarm button does not actuate emergency alarm bell. | 1/17/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair or replace governor to ensure that all moving parts operate freely. | 6/1/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Provide code data plate on disconnect or controller | 9/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Elevator does not recall to fire designated landing when phase 1 key switch is activated to on position. | 12/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | Yes | Governor tripping speed exceeds maximum allowable tripping speed. Governor linkage is corroded. | 12/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.3.4 | Yes | No | Brake will not stop and hold 125% of rated load. Brake linkage can not be adjusted due to chemical corrosion. Brake linkage needs replacement. | 12/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.29 - Car and counterweight safeties | 8.11.2.3.1 | Yes | Yes | Need to perform safety test with rated load on the car | 12/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Machine room door does not open from inside machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide new pit ladder. Existing pit ladder is rusted through. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Bottom landing sill to be maintained flush and level with floor surface of landing | 12/28/2021 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.20.4 | Yes | No | Install a seal on brake tension adjustment along with a metal tag identifying the firm that installed the seal. | 12/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Elevator does not recall to designated landing when phase 1 keyswitch is keyed to on. | |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.1 | No | Yes | Provide ascending car overspeed protection | |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.2 | No | Yes | Provide unintended car movement protection. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | No | No | Provide firefighter phase 2 operation panel cabinet on car operating panel | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | No | No | Hoistway access switches do not function | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Test and log firefighter operation monthly | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | No maintenance records on site | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | No | No | Bottom landing entrance sill is not flush with landing floor. Fill 1 inch gap between landing and entrance sill | |
| A17.1-2016 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(1) Electric elevator, dumbwaiter, or material lift Placed out of Service | Yes | Yes | Elevator has been decommissioned |