Inspection
Inspection Details
Equipment ID
22265
22265
Inspection Date
5/28/2020
5/28/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Charles Brinkman
Charles Brinkman
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
530
530
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
0c45d97c-6574-4101-af95-92d4a9c23462
0c45d97c-6574-4101-af95-92d4a9c23462
Location
West County Middle School
728 HIGHWAY M, PARK HILLS, MO
Phone: (573) 576-3568
728 HIGHWAY M, PARK HILLS, MO
Phone: (573) 576-3568
Owner
Attn: West County R-IV School Distric
West County R-IV School Distric
1122 MAIN ST, LEADWOOD, MO 63653
Phone: (000) 000-0000
Email: kcoffman@wcr4.org
West County R-IV School Distric
1122 MAIN ST, LEADWOOD, MO 63653
Phone: (000) 000-0000
Email: kcoffman@wcr4.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 1) All automatic elevators shall be require a means of two-way communications. Ref: 8.11.2.1.1(f) | 11/16/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | 1) Maintenance records shall document compliance with 8.6 of the Code. There are no maintenance records for this year. Ref: 8.6.1.4.1 | 12/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | 2) Floors and machinery spaces shall be kept free of water, dirt, rubbish, oil, and grease. There is piles of dust and lint on machine room floor. Ref: 8.6.4.8.1 | 12/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | 1) Maintenance records shall document compliance with 8.6 of the Code. There are no maintenance records for this year. Ref: 8.6.1.4.1 | 6/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | 2) Hoistways and pits shall be kept free of dirt and rubbish and shall not be used for storage purposes. Pit needs cleaning. Ref: 8.6.4.7.1 | 6/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | 3) The following documents specified in 8.6.1.2.2(a), (b), and (c) shall be written and permanently kept on-site in the machine room. All testing procedures shall be on site. Ref: 8.6.1.2.2 | 6/27/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. The valve is sealed but not tagged. Based on the installation year of 2014, a category 5 test is due in 2024. | 10/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | Unit has an overspeed valve that is due for a 5-year rated load test this year. | 7/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | No | No | Machine room lights shall work. |