Inspection
Inspection Details
Equipment ID
8843
8843
Inspection Date
3/5/2020
3/5/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
b0654a93-0539-4c61-8b94-e01257bddb3e
b0654a93-0539-4c61-8b94-e01257bddb3e
Location
Gallery 720
720 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 436-1711
720 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 436-1711
Owner
Attn: Brandview LLC
Brandview LLC
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: mgummels@stlluxury.com
Brandview LLC
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: mgummels@stlluxury.com
Billing
Attn: Brandview LLC
Brandview LLC
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: gallery720@stlluxury.com
Brandview LLC
720 Olive St, Apt 2720, St. Louis, MO 63101
Phone: (314) 436-1711
Fax: (314) 436-7348
Email: gallery720@stlluxury.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Test Phase 1 & 2 fire service. | 1/31/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Clean the car top. | 11/10/2020 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | Re-install the car top emergency exit. | 11/10/2020 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | Provide a governor rope cable data tag. | 11/10/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | Seal the hole in the hoistway back wall at the 26th floor. | 11/10/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Replace missing door lock cover at the 22nd floor. | 11/10/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean the pit. | 11/10/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)5 | The pit light shall work. | 11/10/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Replace the bad car top roller. | 11/10/2020 | ||
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | A category 5 test is required. | 1/31/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post the current state operating certificate in the elevator machine room. | 11/10/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)5 | Provide a code compliant pit ladder. | 11/10/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Provide code compliant pit lighting. | 11/10/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Car junction box shall have covers installed. | 11/10/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | Bottom floor door shall have a sight guard. | 11/10/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean. | 11/10/2020 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Properly secure the car top exit. | 11/10/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | The car top shall be cleaned and kept clean. | 11/10/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | 22nd floor and 31st floor interlocks shall have covers. | 3/5/2020 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | Properly cover hole in rear of hoistway at 26th floor. | 11/10/2020 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | The machine room shall be kept clean. | 11/10/2020 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Provide adequate lighting at the hoist machine. | 11/10/2020 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase 1 fire service shall properly operate. (Completed March 5th) | 3/5/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase 2 fire service shall be tested. (Completed March 5th) | 3/5/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Clean the car top. | 11/10/2020 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Re-install and properly secure the car top emergency exit. | 11/10/2020 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | Provide a governor rope cable data tag. | 11/10/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | Seal the hole in the hoistway back wall at the 26th floor. | 11/10/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Replace missing door lock cover at the 22nd and 31st floors. | 11/10/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean the pit. | 11/10/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | The pit light shall be operational. | 11/10/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Replace the bad car top roller. | 11/10/2020 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post the current state operating certificate in the elevator machine room. | 11/10/2020 | ||
| MO Minimum : Elevators | (I) - Pits | (I)5 | Provide a code compliant pit ladder. | 11/10/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Car junction box shall have covers installed. | 11/10/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | Bottom floor door shall have a sight guard. | 11/10/2020 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | The machine room shall be kept clean. | 11/10/2020 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Provide adequate lighting at the hoist machine. | 11/10/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide a code compliant MCP including onsite documents. | 5/3/2021 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO state operating certificate shall be displayed in the elevator machine room. | 5/3/2021 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | Provide a governor rope data tag. | 5/3/2021 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | The car shall level properly with the landing at the 31st floor. | 5/6/2021 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | The car top exit shall be secured so that it can only be opened from the top of the car without the use of tools. | 5/3/2021 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | The machine room door shall be self-closing and self-locking. | 5/3/2021 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | The car shall level properly with the landing at the 31st floor. The car must level within 1/2" of the landing sill. | 1/12/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | The car shall level properly with the landing at the 31st floor. The car must level within 1/2" of the landing sill. (Uncleared Violation requiring re-inspection from 2021) | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service test charts are missing. | 12/19/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | The front door closing force exceeds 30 lbs. | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | All electrical wiring shall be enclosed per NFPA70. | 12/19/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Clearance from car door equipment on side entrance shall be maintained from hoistway door equipment. | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Check integrity of control circuits that have temporary jumpers installed. | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Firemans' return shall properly function. Elevator Red Tagged. |