Inspection
Inspection Details
Equipment ID
23290
23290
Inspection Date
6/12/2020
6/12/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20
20
External ID
9866a9d6-723b-486d-ad67-48c2009417cf
9866a9d6-723b-486d-ad67-48c2009417cf
Location
SSM Healthcare
711 VETERANS MEMORIAL PKWY, SAINT CHARLES, MO
711 VETERANS MEMORIAL PKWY, SAINT CHARLES, MO
Owner
Attn: Plant Operation
SSM Health St. Joseph Hospital - St. Charles
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (314) 989-6134
Email: Ronald.Obrien@ssmhealth.com
SSM Health St. Joseph Hospital - St. Charles
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (314) 989-6134
Email: Ronald.Obrien@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. | 8/26/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | There is no fire extinguisher near the controller space, as required. Provide an ABC type extinguisher of proper size for the room. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The current state operating certificate needs to be posted near the controller space in a non-combustible frame. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | There is no fire extinguisher near the controller space, as required. Provide an ABC type extinguisher of proper size for the room. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The current state operating certificate needs to be posted near the controller space in a noncombustible frame. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and door pressure recorded before the inspection is completed. | 8/9/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of construction. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection Required. |