Inspection
Inspection Details
Equipment ID
21049
21049
Inspection Date
6/1/2020
6/1/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
205c8160-f0b2-4eee-bcb8-0ecab09942fb
205c8160-f0b2-4eee-bcb8-0ecab09942fb
Location
Fresh Properties (Abstrakt Marketing Group)
800 LUMIERE PLACE BLVD, SAINT LOUIS, MO
Phone: (618) 482-8712
Alt Phone: (314) 575-4633
800 LUMIERE PLACE BLVD, SAINT LOUIS, MO
Phone: (618) 482-8712
Alt Phone: (314) 575-4633
Owner
Attn: John Cusamano Jr
Fresh Properties
416 N 23rd Street, St. Louis, MO 63103
Phone: (618) 482-8712
Alt Phone: (314) 575-4633
Fresh Properties
416 N 23rd Street, St. Louis, MO 63103
Phone: (618) 482-8712
Alt Phone: (314) 575-4633
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. | 6/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2018 | 4/30/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The elevator hoistway shall be fully enclosed. Inside the hoistway drywall has become dislodged due to flooding that shall be repaired and the elevator shaft shall retain its hoistway fire rating. | 4/30/2021 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | The belts on the hydraulic pump motor are cracked and worn unevenly. Replace belts for a smooth operation of pump to motor. | 4/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Second Notice | 3/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.16.3 | Yes | No | A cross head data plate shall be provided. | 3/8/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | There is an unknown pipe protruding from the pit floor. The pipe shall be removed or a variance applied for. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | Yes | No | Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Yes | No | A monthly fire service testing log shall be provided. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Yes | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall operate properly. | 3/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 3/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | MAchine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The up to date State operating certificate must be displayed. |