Inspection
Inspection Details
Equipment ID
19258
19258
Inspection Date
6/18/2018
6/18/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
Iatan Station
20256 Hwy 45 North, Weston, MO
Phone: (816) 386-2047
20256 Hwy 45 North, Weston, MO
Phone: (816) 386-2047
Owner
KC Power & Light
1201 Walnut, Kansas City, MO 64141-9679
1201 Walnut, Kansas City, MO 64141-9679
Billing
Attn: Iatan Power Plant
20250 Hwy 45 N, , MO 64098-8902
20250 Hwy 45 N, , MO 64098-8902
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Doors do not close on fire service phase 2. | 4/3/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | Provide code data plate and display on disconnect or controller.. | 9/16/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Test and log firefighter operation monthly | 9/18/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Post emergency evacuation of passengers procedure in machine room | 9/18/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.3 - Top-of-car operating device | 8.11.2.1.3(c) | Top of car inspection station will not run car while on top of car inspection operation | 9/18/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Machine room air conditioning unit is not cooling the machine room. | 9/18/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Provide firefighter cabinet on car operating panel | 5/17/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | Post code data plate on controller or disconnect | 9/16/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | x | Provide firefighter cabinet on car operating panel | 5/23/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Current state operating certificate not displayed | 9/16/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | post code data plate on controller or disconnect. "ASME A17.1 2004" | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | state operating certificate not displayed | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | x | Repair the emergency phone. | |
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Repair the pit light. |