Inspection
Inspection Details
Equipment ID
18471
18471
Inspection Date
6/9/2020
6/9/2020
Inspection Type
Alteration
Alteration
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
238cfc47-8877-414b-bbf5-b5c8cffb2747
238cfc47-8877-414b-bbf5-b5c8cffb2747
Location
City Place 5
845 N NEW BALLAS CT, CREVE COEUR, MO
Phone: (314) 993-5800
845 N NEW BALLAS CT, CREVE COEUR, MO
Phone: (314) 993-5800
Owner
Attn: SNH Medical Office Properties Trust c/o RMR Real Estate Service
SNH Medical Office Properties Trust c/o RMR Real Estate Service
1660 Lincoln Street, Ste 1910, Denver, CO 80264
Phone: (314) 392-0400
Email: Kristen.Hinzman@cushwake.com
SNH Medical Office Properties Trust c/o RMR Real Estate Service
1660 Lincoln Street, Ste 1910, Denver, CO 80264
Phone: (314) 392-0400
Email: Kristen.Hinzman@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/1/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/1/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/26/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | Yes | No | Fire service phase II switch key shall not be removable in "ON" position. | 5/1/2026 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Yes | No | Machine room oil coolers are wired to cab lighting circuit. Shall be dedicated circuits. | 5/1/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/1/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Missing PM/repair/callback/testing logs for 2023, 2024 and 2025. | 5/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (1st Floor). | 5/1/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Replace unreadable in-car capacity plate/unit number plate. | 5/1/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be documented monthly. | 5/1/2026 |