Inspection
Inspection Details
Equipment ID
19313
19313
Inspection Date
6/16/2020
6/16/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
David Tiemann
David Tiemann
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
16
16
External ID
fd41f879-d69a-4582-afca-b1abb6749631
fd41f879-d69a-4582-afca-b1abb6749631
Location
100 North Tucker Bldg
100 N TUCKER BLVD, SAINT LOUIS, MO
Phone: (314) 977-2966
100 N TUCKER BLVD, SAINT LOUIS, MO
Phone: (314) 977-2966
Owner
Attn: UNK
St. Louis University
3545 LINDELL BLVD 2nd Floor, SAINT LOUIS, MO 63103
Phone: (314) 977-2966
Email: barth.breneman@slu.edu
St. Louis University
3545 LINDELL BLVD 2nd Floor, SAINT LOUIS, MO 63103
Phone: (314) 977-2966
Email: barth.breneman@slu.edu
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Door Edge is not overridden on Phase 1 and 11 | 5/8/2019 | |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Suspension ropes need to be shortened. | 6/16/2020 | |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)2 | Anti spin-out cable is broken. Needs to be replaced. | 2/2/2021 | ||
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Door does not stay open during Phase II. | 6/16/2020 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Wrong key switch is in car for fire service. | 6/16/2020 | |
MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | x | In car pull stop switch needs to be tied into the alarm bell. | 6/16/2020 | |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | x | Suspension ropes need to be shortened. Car does not make up final limit on car top inspection. RED TAGGED. | 9/23/2020 |
MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | Anti spin out cable is broken. | 2/2/2021 | ||
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Door does not stay open during Phase I operation. RED TAGGED. | 9/23/2020 |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency alarm and bell do not work. | 9/23/2020 | |
MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | x | In car pull top switch needs to be accompanied by an alarm when activated. | 9/23/2020 | |
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room illumination shall be 19fc minimum | 11/5/2024 | |
MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | x | All fire recall switches in a building shall be keyed alike | 11/5/2024 | |
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Supply permanent power to rescue phone. Extension cords do not meet the NFPA 70 codes | 11/5/2024 | |
A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | x | Standard receptical in the elevator cab shall be removed or replaced with a GFIC receptacle | 11/5/2024 | |
A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.5 | x | Repair and retest the Shunt trip circuit | 11/5/2024 | |
A17.1-2016 : Elevators | 2.12 - Controller Wiring, Fuses, Grounding, Etc. | 2.26.1 | Shunt trip currently not functioning when car is on Fire recall bypass | |||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | All elevators in a single building shall have Firerecall switches keyed alike | |||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys | x | All Fire recall key switches shall be keyed alike within 30 days. (12/20/24) |