Inspection
Inspection Details
Equipment ID
12668
12668
Inspection Date
6/3/2020
6/3/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
e134415e-4eb4-406b-ad4f-a06f59e74571
e134415e-4eb4-406b-ad4f-a06f59e74571
Location
West County Center
44 W COUNTY CTR, DES PERES, MO
Phone: (314) 288-2020
44 W COUNTY CTR, DES PERES, MO
Phone: (314) 288-2020
Owner
Attn: Mike Baker
CBL Properties/West County center
80 West County Center, Des Peres, MO 63131
Phone: (314) 288-2034
Email: mike.baker@cblproperties.com
CBL Properties/West County center
80 West County Center, Des Peres, MO 63131
Phone: (314) 288-2034
Email: mike.baker@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace broken step chip | 10/8/2019 |
| conversion | conversion | n/a | No | No | Repair alarm on top stop switch cover | 10/8/2019 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 806.2 | No | No | Upper and lower demarcation lights are not working. Repair | 10/8/2019 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Upper level machine spaces need to be cleaned out. | 10/8/2019 |
| A17.1-1996 : Escalators | 8.2 - Stop switch | 210.2 | No | No | Upper level stop switch buzzer does not work. | 10/8/2019 |
| A17.1-1996 : Escalators | 7.15 - Balustrades | 802.3 | No | No | Upper left clamping strip is broken. Needs to be replaced. | 10/8/2019 |
| A17.1-1996 : Escalators | 7.15 - Balustrades | 802.3 | No | No | Bottom right deck guard is missing and left side is at wrong height. | 10/8/2019 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 801.1 | No | No | Replace broken stop. Step tread is broke off. | 10/8/2019 |
| A17.1-1996 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 1206.6a | No | No | Pit needs to be cleaned. | 9/28/2020 |
| A17.1-1996 : Escalators | 7.10 - Operating and safety devices | 805.3a | No | No | Stop switch buzzer on top not working. | 9/28/2020 |
| A17.1-1996 : Escalators | 8.4 - Drive machine and brake | 804 | Yes | Yes | Brake solenoid failed, replace. Re-inspection required | 3/20/2023 |
| A17.1-1996 : Escalators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(3) Escalators Placed out of Service | Yes | Yes | Step indexing & comb plate impact devices need testing, brake solenoid needs replaced | 3/20/2023 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 1008.2m Handrails | No | No | Left handrail has cracks with pinch points and shall be replaced | 11/12/2025 |
| A17.1-1996 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 1008.2s | No | No | Adjust top right skirt for proper clearance | 8/13/2026 |
| A17.1-1996 : Escalators | 7.4 - Entrance and egress ends | 802.12 | No | No | Repair inoperative demarcation lights | 8/13/2026 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 801.1 | No | No | Clean down Truss | 8/13/2026 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 1008.2m Handrails | Yes | No | Left handrail has cracks with pinch points and shall be replaced | 8/13/2026 |