Inspection
Inspection Details
Equipment ID
11769
11769
Inspection Date
5/22/2020
5/22/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
6fdf79fd-bc53-4bd9-8823-76a0d93df345
6fdf79fd-bc53-4bd9-8823-76a0d93df345
Location
Beauvai's Manor on the Park
3625 MAGNOLIA AVE, SAINT LOUIS, MO
Phone: (314) 771-2990
3625 MAGNOLIA AVE, SAINT LOUIS, MO
Phone: (314) 771-2990
Owner
Attn: Ashley Call
Beauvais Manor on the Park
3625 MAGNOLIA AVE, SAINT LOUIS, MO 63110
Phone: (314) 771-2990 Ext: 248
Email: acall@beauvaismanor.com
Beauvais Manor on the Park
3625 MAGNOLIA AVE, SAINT LOUIS, MO 63110
Phone: (314) 771-2990 Ext: 248
Email: acall@beauvaismanor.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Car two way communication shall be operational. | 7/12/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/27/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Holes in front hoistway wall shall be sealed with approved solid material. | 10/27/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Remove the unsupported wiring in the hoistway which is not necessary for the operation of the elevator. | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 11/5/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/14/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 6/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | No evacuation procedure in MCP. | 12/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/11/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and free of dirt and rubbish. | 12/11/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | In electrical equipment rooms, the illumination shall not be controlled by automatic means. This switch is currently a motion sensor which could turn off unexpectedly with the technician in the room. | 12/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car alarm bell shall be operational on auxiliary power. | 12/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power must be tested annually. | 5/22/2026 |