Inspection
Inspection Details
Equipment ID
7508
7508
Inspection Date
5/27/2020
5/27/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
20"
20"
Governor Rope Pull
90/610
90/610
Door Closing Force
20
20
External ID
95d47304-89ff-4c47-b40f-34f4b28049a9
95d47304-89ff-4c47-b40f-34f4b28049a9
Location
Courtyard by Marriott
827 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 231-7560
827 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 231-7560
Owner
Attn: Courtyard by Marriott
Courtyard by Marriott
827 WASHINGTON AVE, SAINT LOUIS, MO 63101
Phone: (314) 418-5840
Email: rodney.anderson@marriott.com
Courtyard by Marriott
827 WASHINGTON AVE, SAINT LOUIS, MO 63101
Phone: (314) 418-5840
Email: rodney.anderson@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | 1206.2c - Clean the car top. | 10/8/2019 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean the pit. | 10/8/2019 | ||
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | The pit shall be kept clean and dry. | 7/22/2020 | ||
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | The sump pump in the pit shall be operational. | 7/22/2020 | ||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide a code compliant MCP including onsite documents. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | The car door restrictor shall be operational. | 2/22/2022 | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit shall be kept clean. Clean the pit. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The phone is hard to hear due to static. Take corrective action as needed. | 2/23/2022 | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 2/23/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Inspection of the hoistway and fire service need to be tested to complete the annual inspection. | 2/23/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The emergency power indicator light shall activate when unit is operating on emergency power. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 1001.2(c)(18) | The basement level interlock conduit shall be repaired. | 7/10/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The pickup rollers at B & 1 shall be adjusted for proper operation. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | The car top shall be kept clean. Clean the car top. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The phone is hard to hear due to static. Take corrective action as needed. | 1/24/2023 | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | The car-top shall be kept clean. Clean the car top. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | The pit shall be kept clean. Clean the pit. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 102 | The basement level interlock conduit shall be repaired or replaced. | 7/10/2024 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | The standby/emergency power indicator light at the egress floor shall illuminate when on emergency power operation. | 3/6/2024 | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | The car-top shall be kept clean. Clean the car top. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | The pit shall be kept clean. Clean the pit. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 102 | The basement level interlock raceway shall be repaired or replaced. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | The car top shall be cleaned. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Car door restrictor is missing. | 7/15/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Pick up roller on floor 1 door needs adjusting. | 7/10/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | x | Car top handrail is bent. | 7/15/2024 | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | There is water in the pit. The pit shall be kept clean and dry. Correct source of water leak. | 7/10/2024 | ||
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | The in car emergency light shall be operational. Repair or replace as needed. | 7/15/2024 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency bell does not work. | 7/15/2024 | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and related on-site documentation shall be provided in the machine room. MCP hasn't been updated since 2022. | |||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Pit shall be kept clean. Remove excess debris. | |||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | Cartop shall be kept free of excess debris/dirt/lint. | |||
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | Machine room lighting needs to be repaired, 1 or more bulbs not working. | |||
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | Machine room door shall be self-closing and self-locking . There is no handle/lock on MR door. | |||
| A17.1-1996 : Elevators | 3.22 - Wire rope fastening and hitch plate | 212 | .9e(4) - Hoist Rope Tail retaining clips shall be properly spaced. Counterweight side. | |||
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | There is a large amount of "Rope Dust" on the floor by the machine. Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM | ||
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | 110.11f(2) - Hoistway doors have loose guides on 7th floor. Repair/replace as needed. | |||
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | 110.11f(3) - Hoistway door gib fire tabs shall be engaged into the guideway(sill) : 8th floor. | |||
| A17.1-1996 : Elevators | 2.16 -Overhead Beam and Fastenings | 105.3 | Top of hoistway beam clamp has loose jamb nut (about to fall off bolt). |