Inspection
Inspection Details
Equipment ID
13072
13072
Inspection Date
6/18/2020
6/18/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
600
600
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
504b3ac7-83bc-4171-b9c4-7621f754b1d9
504b3ac7-83bc-4171-b9c4-7621f754b1d9
Location
Friendly Temple Apartments
5545 WELLS AVE, SAINT LOUIS, MO
Phone: (314) 367-9700
5545 WELLS AVE, SAINT LOUIS, MO
Phone: (314) 367-9700
Owner
Friendly Temple Apartments
5545 WELLS AVE # 5521, SAINT LOUIS, MO 63112-4237
5545 WELLS AVE # 5521, SAINT LOUIS, MO 63112-4237
Billing
Attn: Friendly Temple Apartments
5545 WELLS AVE # 5521, SAINT LOUIS, MO 63112-4237
5545 WELLS AVE # 5521, SAINT LOUIS, MO 63112-4237
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Repair machine room ventilation | 8/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair phone in car | 10/6/2021 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | Repair machine room ventilation | 10/13/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Overspeed valve is overdue for full load testing | 3/13/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | Repair machine room ventilation | 3/13/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 3/13/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications phone in car not working | 3/10/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/13/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Provide existing battery backup lowering unit to work properly. | 6/2/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Failed Cat 1 standby power test. Re-inspection required |