Inspection
Inspection Details
Equipment ID
24540
24540
Inspection Date
3/18/2019
3/18/2019
Inspection Type
Initial Inspection
Initial Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Andrew Smith
Andrew Smith
Relief Valve Pressure
0
0
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
0
0
External ID
cf84fc6a-34f2-4196-995a-1c72ba54889c
cf84fc6a-34f2-4196-995a-1c72ba54889c
Location
Smithton United Methodist Church
300 Walnut Street, Smithton, MO
Phone: (660) 343-5560
300 Walnut Street, Smithton, MO
Phone: (660) 343-5560
Owner
Attn: Smithton United Methodist Church
Smithton United Methodist Church
300 Walnut Street, Smithton, MO 65350
Phone: (660) 343-5560
Smithton United Methodist Church
300 Walnut Street, Smithton, MO 65350
Phone: (660) 343-5560
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Enclose all hoistway wiring in approved conduit. | 8/3/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Provide pit switch, for elevator personell in pit. | 8/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light and bell not working | 6/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP needed | 6/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire don't use elevator signage needed | 6/14/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Pit needs stop switch | 3/14/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Hoistway door to sill clearance over 3/4 in. | 4/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car gate panels are separating on both front and rear . Need replaced | 3/14/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Pit needs stop switch. Told it's planned. | 3/14/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Hoistway door to sill clearance over 3/4 inch. Baffles are on site and planned to be installed | 9/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car gate panels separating | 3/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car accordion doors gaping open @ hinges. Repair or replace doors. | 3/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency phone and alarm bell not working. Need battery and bldg line repaired. Bldg aware and addressing. |