Inspection
Inspection Details
Equipment ID
20220
20220
Inspection Date
6/9/2020
6/9/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
27
27
External ID
93ac4aa9-b1da-400b-848c-2d4b88e3bac0
93ac4aa9-b1da-400b-848c-2d4b88e3bac0
Location
River City Casino
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO
Phone: (314) 388-7777
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO
Phone: (314) 388-7777
Owner
Attn: River City Hotel
PNK (River City) LLC
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO 63125
Phone: (314) 681-9894
Email: Charles.sheard@rivercity.com
PNK (River City) LLC
777 RIVER CITY CASINO BLVD, SAINT LOUIS, MO 63125
Phone: (314) 681-9894
Email: Charles.sheard@rivercity.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove all unrelated storage from elevator equipment room. | 11/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 6/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab is not working, line problem. Re-inspection required | 4/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required in 14 days. | 5/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA phone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 6/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following tests need to be performed to complete inspection: full load, full speed safeties, unintended movement, fire service, safeties pull out, governor pull thru & 125% brake. Re-inspection required | 7/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check & repair the programming of this phone for proper operation and passenger safety. Re-inspection required | 7/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Test failed, need to perform the following tests to complete Cat 5 full load test: Test car safeties with rated load at rated speed, test governor rope pull thru force, Perform unintended movement test. Test drive machine brake with 125% of rated load. Phase I & II fire service. Unit Red-tagged, Re-inspection required | 8/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not operating correctly. Re-inspection required | 8/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair programming of the phone for proper operation and passenger safety. Note: This phone has not been operational since 6/2022. Elevator Red Tagged due to this issue. | 10/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power needs to be tested. Re-inspection required | 4/9/2025 |