Inspection
Inspection Details
Equipment ID
9656
9656
Inspection Date
6/24/2020
6/24/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
888b49ef-8e28-464e-aa04-589d58562a26
888b49ef-8e28-464e-aa04-589d58562a26
Location
De Paul Health Center
12255 DE PAUL DR, BRIDGETON, MO
Phone: (314) 344-6102
12255 DE PAUL DR, BRIDGETON, MO
Phone: (314) 344-6102
Owner
Attn: Andrew Gratton
De Paul Health Center
12303 DE PAUL DR, BRIDGETON, MO 63044
Phone: (314) 989-6134
Email: Andrew.Gratton@ssmhealth.com
De Paul Health Center
12303 DE PAUL DR, BRIDGETON, MO 63044
Phone: (314) 989-6134
Email: Andrew.Gratton@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | No | No | The emergency light fixture inside the elevator has a broken glass cover plate that is a potential cutting hazard to passengers. Replace broken cover plate, no reinspection required. | 7/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | There are a number of Braille floor indicating/push button tags that are missing on multiple floors and shall be reinstalled for proper floor identification. | 7/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The tension on the hoist ropes is not equal which is resulting in unequal wear of the hoist ropes and the main drive sheave. Properly tension the hoist ropes. | 6/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The unintended motion, fireman’s service, and emergency power testing shall be performed before the inspection is completed. | 6/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | 6/22/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 6/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. | 6/11/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. Re-inspection required | 6/22/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | The counterweight runby is 2" due to rope stretch. Remove blocking from bottom of counterweight or shorten suspension cables to maintain 6" minimum of runby. Re-inspection required | 7/29/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. Re-inspection required | 7/29/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | When testing the elevator on emergency power, the emergency power jewel failed to illuminate, needs repaired. Re-inspection required | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | When testing phase I fire service, the visual indicator light failed to illuminate, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | The counterweight runby is 2" due to rope stretch. Remove blocking from bottom of counterweight or shorten suspension cables to maintain 6" minimum of runby. Re-inspection required |