Inspection
Inspection Details
Equipment ID
13350
13350
Inspection Date
6/24/2020
6/24/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Michael Barnhart
Michael Barnhart
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
bc142431-b904-4f25-ab61-4f050656f503
bc142431-b904-4f25-ab61-4f050656f503
Location
Townsend & Wall Lofts
602 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 390-9994
602 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 390-9994
Owner
Attn: Townsend & Wall Lofts
Townsend & Wall Lofts
602 Francis St, St. Joseph, MO 64501
Phone: (816) 279-4101
Fax: (816) 390-9994
Email: townsendwall@fairwaymanagement.com
Townsend & Wall Lofts
602 Francis St, St. Joseph, MO 64501
Phone: (816) 279-4101
Fax: (816) 390-9994
Email: townsendwall@fairwaymanagement.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency light and bell do not operate | 6/24/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | Repair or replace air conditioner in order to provide adequate temperature for equipment in machine room. | 6/24/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need to test fire service operation monthly and keep a record log of testing on site. | 6/24/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Fire service phase 2 operation does function. 14 days to correct or elevator will be red tagged. | 6/24/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Need to have fire service key on site and accessible. | 6/24/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 6/19/2023 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Replace illegible identification markings on phase 1 and phase 2 firefighter keyswitches | 6/19/2023 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.7.2.19 | Yes | No | New governor is the wrong speed/size for car. Car is rated for 200FPM, new governor is rated for a car speed of 350FPM. Testing halted. | 5/16/2024 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.7.1.8 | Yes | No | Provide code data plate on controller. | 5/16/2024 |
| A17.1-2016 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 2.14.1.7.1 | Yes | No | Provide a car top railing system. | 5/16/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | Yes | No | Fire hat not working on COP during fire testing. | 5/16/2024 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 2.29.1 | Yes | No | Label controller, disconnects, and machine with elevator ID#. (Car 1) | 5/16/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | REPAIR NON-WORKING LIGHTS IN MACHINE ROOM | 10/9/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | REPLACE BAD HOIST ROPES | 10/9/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | REPAIR NON-WORKING IN CAR EMERGENCY PHONE | 10/9/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | No | No | 8.6.4.13.1 (d) REPLACE MISSING VISION PANELS ( SIGHT GUARDS ) ON HOISTWAY DOORS | |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.18.4 | Yes | No | 2.18.9 A METAL PLATE SHALL BE SECURELY ATTACHED TO EACH SPEED GOVERNOR AND SHAL BE MARKED IN A LEGIBLE AND PERMANENT MANNER WITH LETTERS AND FIGURES NOT LESS THAN 6mm ( 0.25 in ) IN HEIGTH INDICATING TRIP SPEED, SIZE OF GOVERNOR ROPE, PULL-THROUGH, MANUFACTURERS NAME & THE WORDS "DO NOT LUBRICATE GOVERNOR ROPE" |