Inspection
Inspection Details
Equipment ID
19914
19914
Inspection Date
5/13/2020
5/13/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Jason Turner
Jason Turner
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
2fa48910-c051-406f-a0e2-37f4409a400e
2fa48910-c051-406f-a0e2-37f4409a400e
Location
Arrowhead Stadium
1 ARROWHEAD DR, KANSAS CITY, MO
Phone: (816) 921-3600
1 ARROWHEAD DR, KANSAS CITY, MO
Phone: (816) 921-3600
Owner
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129-1651
1 ARROWHEAD DR, KANSAS CITY, MO 64129-1651
Billing
Attn: Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129-1651
1 ARROWHEAD DR, KANSAS CITY, MO 64129-1651
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | replace the car gate astragals on both the front and rear gates, they are both torn | 5/13/2020 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | The Maintenance Control Program On-Site documents are not in the machine room. | 7/28/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/28/2025 | ||
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | Machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually. | 7/28/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. | 7/28/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. | 7/28/2025 | ||
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | x | the alarm bell did not work on battery power or on 110volt power, replace alarm bell battery | 6/7/2022 | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 7/28/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | Did not have a written record of the maintenance performed on this elevator in the machine room. | 7/28/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | emergency phone continues to ring even after answering service answers the phone, the ringing makes two way conversation next to impossible | 11/14/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 8.11.2.1.1(g) | replace the rubber astragals on both the front and rear vertical sliding car gates - 8.6.4.13.1(g) | 7/28/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.9 - Power closing of doors or gates | 2.13.3 | Replace hoistway door chain on floor #2 it corroded and no longer bends over the drive motor and doesn’t fully open the doors and faults out |