Inspection
Inspection Details
Equipment ID
14947
14947
Inspection Date
6/2/2020
6/2/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Kurt Warttig
Kurt Warttig
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
7eb4ae45-35d6-4712-836f-62bfc11a126e
7eb4ae45-35d6-4712-836f-62bfc11a126e
Location
Administration Center
280 Interstate Dr, Wentzville, MO
Phone: (636) 327-3858 Ext: 21323
Email: lindabagby@wsdr4.org
280 Interstate Dr, Wentzville, MO
Phone: (636) 327-3858 Ext: 21323
Email: lindabagby@wsdr4.org
Owner
Attn: Linda Bagby
Wentzville R-IV School District
1 Campus Dr, Wentzville, MO 63385
Phone: (636) 327-3858 Ext: 21323
Email: lindabagby@wsdr4.org
Wentzville R-IV School District
1 Campus Dr, Wentzville, MO 63385
Phone: (636) 327-3858 Ext: 21323
Email: lindabagby@wsdr4.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written maintenance control program shall be kept on site | 3/8/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Reprogram emergency phone | 7/18/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Failed Phase I recall, has no Phase II | 2/21/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean pit. | 3/8/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from the sump hole. | 3/8/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Determine if sump pump works correctly, if not replace. | 3/8/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/11/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Sump hole is filled with oil, needs to be removed | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to determine if sump pump works correctly, if not it needs to be replaced | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Sump hole is filled with oil, need to remove | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to determine if the sump pump is working correctly, if not repair or replace |