Inspection
Inspection Details
Equipment ID
18325
18325
Inspection Date
6/18/2020
6/18/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
3c8b27e2-afcb-4db1-aba2-701c641808f6
3c8b27e2-afcb-4db1-aba2-701c641808f6
Location
Tesson Ferry Building
12122 TESSON FERRY RD, SAINT LOUIS, MO
Phone: (314) 965-9160
12122 TESSON FERRY RD, SAINT LOUIS, MO
Phone: (314) 965-9160
Owner
E & M Development
11600 MANCHESTER RD, DES PERES, MO 63131-4619
11600 MANCHESTER RD, DES PERES, MO 63131-4619
Billing
Attn: E & M Development
11600 MANCHESTER RD, DES PERES, MO 63131-4619
11600 MANCHESTER RD, DES PERES, MO 63131-4619
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. | 10/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 2/22/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 6/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not work. | 10/11/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone needs to be reprogrammed. | 10/11/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | SOS malfunctioned during testing. Take corrective action and re-test. | 10/11/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. This phone was also not operational on 6/14/2024. The phone shall be made operational immediately or the unit will have to be red tagged and locked out of service. | 4/10/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unintended car movement detection system shall be tested. The unique testing procedures not on-site, unable to test. Unit is a 1st generation TK ISIS with steel cable conversion with machine mounted in pit. | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | In car emergency lighting shall work. | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine room shall have proper fire extinguisher and shall have a current monthly/annual test tag. | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current Missouri State operating certificate shall be obtained and displayed in the equipment room in a non-combustible frame. Note: The 2016 certificate is displayed. | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | No | No | Means of manual release of braking system, as permitted by A17.1-2004 2.24.8.4 and required by A17.1S-2005 2.7.6.4 shall be tested. Unique testing procedures not on-site, unable to test. | 5/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Unique testing procedures for the TK ISIS shall be on-site. | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | In car emergency lighting shall work. | 7/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine room shall have proper fire extinguisher and shall have a current monthly/annual test tag. | 7/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current Missouri State operating certificate shall be obtained and displayed in the equipment room in a non-combustible frame. Note: The 2016 certificate is displayed. | 7/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | No | No | Means of manual release of braking system, as permitted by A17.1-2004 2.24.8.4 and required by A17.1S-2005 2.7.6.4 shall be tested. Unique testing procedures not on-site, unable to test. | 7/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Unique testing procedures for the TK ISIS shall be on-site. | 7/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in the machine room in a non-combustible frame. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine room shall have proper fire extinguisher and shall have a current monthly/annual test tag. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device is not functioning and needs repaired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | In car emergency lighting shall work. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Unique testing procedures for the TK ISIS shall be on-site. |