Inspection
Inspection Details
Equipment ID
9748
9748
Inspection Date
6/29/2020
6/29/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Benjamin Williams
Benjamin Williams
Relief Valve Pressure
330
330
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
02575871-dcdd-49ce-9c5a-00081cf9b4e4
02575871-dcdd-49ce-9c5a-00081cf9b4e4
Location
Park Station Apartments
5560 PERSHING AVE, SAINT LOUIS, MO
Phone: (314) 361-8300
5560 PERSHING AVE, SAINT LOUIS, MO
Phone: (314) 361-8300
Owner
Attn: Park Station Apartments
Kilamanjaro I
P O Box 28514, SAINT LOUIS, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Kilamanjaro I
P O Box 28514, SAINT LOUIS, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Billing
Attn: Revival STL
Revival STL
P O Box 46721, SAINT LOUIS, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Revival STL
P O Box 46721, SAINT LOUIS, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Car emergency telephone does not work. Needs to be programmed to a 24 hour source. | 2/20/2019 |
| conversion | conversion | n/a | No | No | Fix the oil leak either on the valve or pump, or both. | 4/19/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No maintenance control program. Provide electrical prints for controller. | 7/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | No fire extinguisher in machine room. | 7/1/2020 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | Repair oil leaks under the tank. | 7/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/18/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" | 9/10/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Need fire extinguisher in machine room | 9/3/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Change Fire Service Phase II key switch to "ON" and "OFF" only. Does not have "HOLD" operation. | 12/5/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | At some point the elevator control operating panel (cop) has been replaced. At the time of installation this elevator was required to have either a audio or visual signal indicating when the phase 1 fireman service operation was activated. Install either an audio or visual signal to activate with fireman service phase I operation. | 12/5/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | A light fixture in the elevator cab was not operational on the day of inspection. Repair light fixture to provide adequate lighting. | 2/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. | 2/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The lighting in the elevator machine room is not sufficient. The lighting shall not be less than (10) foot candles at the floor level. | 2/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 2/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 2/15/2026 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | The belts on the hydraulic pump motor are mismatched and worn unevenly. Replace belts for a smooth operation of pump to motor. | 2/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. | 2/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean Elevator pit | 2/15/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit access door shall be kept closed and locked | 2/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove unnecessary materials from the machine room | 2/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room door shall be kept closed and locked. Door shall be self closing and self locking | 5/13/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Close hoistway wall penetrations | 2/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine Room door shall be self closing and self locking. Needs knob and lock. | 2/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Fire Service module in machine room shall be properly mounted. | 2/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Hole in Machine Room wall shall be repaired | 2/15/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine Room lights shall be installed per NEC and provide 10 foot candles | 2/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire Extinguisher shall be kept up to date | 2/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be cleaned (oil) | 2/15/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Holes in overhead shall be sealed (previously a traction elevator) | 2/15/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Repair the ventilation cover at the top of the hoistway | 2/15/2026 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 2.11 | Yes | No | Transition between the landing sill and the tile/carpet exceeds 1" and creates a trip hazard. Floor transition shall be beveled or decreased to less than 1/4" | 3/25/2026 |