Inspection
Inspection Details
Equipment ID
20159
20159
Inspection Date
6/1/2020
6/1/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Donald Brown
Donald Brown
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
23
23
External ID
fe9786df-919a-491e-a211-d17fa2583054
fe9786df-919a-491e-a211-d17fa2583054
Location
Johnson Hall
5000 OAK ST, KANSAS CITY, MO
Phone: (816) 235-1363
5000 OAK ST, KANSAS CITY, MO
Phone: (816) 235-1363
Owner
Attn: UMKC- Campus Facilities Mgmt
UMKC- Campus Facilities Mgmt
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (816) 235-1363
Email: hickmanch@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (816) 235-1363
Email: hickmanch@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | replace the capacity sign on the car operating panel, it can no longer be read | 6/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.16 - Rated load, platform area, and data plate | 8.11.2.1.1(p) | No | No | replace missing capacity sign in the elevator cab | 6/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the state operating certificate in the machine room | 6/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Post monthly fire service test log in the machine room | 6/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide access to the complete MCP in the machine room according to 8.6 | 6/19/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.3.1 Capacity Plates | No | No | replace missing capacity sign on car operating panel | 6/19/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. the one on display in the machine room is from 2014 | 6/19/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | The Maintenance Control Program On-Site documents are not in the machine room. | 6/19/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | monthly fire service test log is missing from the machine room | 6/19/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2015 | 6/19/2026 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 8.11.3.1.3(l) | No | No | the smoke damper at the top of the hoistway is open, it is only to open when the hoistway smoke detector is activated or when the damper motor fails, repair or replace the motor for the smoke damper (A17.1-2016 [2.1.4]) | 6/19/2026 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.3.1.2(f) | No | No | top of hoistway machine space light is burnt out, replace burnt out light bulb (A17.1-2016 [2.7.9.1]) | 6/19/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 6/19/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 8/12/2026 |