Inspection
Inspection Details
Equipment ID
21837
21837
Inspection Date
6/17/2020
6/17/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
ecb72695-e3cd-4713-8c26-170e7c6d6133
ecb72695-e3cd-4713-8c26-170e7c6d6133
Location
3728 Market Bldg
3728 MARKET ST, SAINT LOUIS, MO
Phone: (314) 614-2356
3728 MARKET ST, SAINT LOUIS, MO
Phone: (314) 614-2356
Owner
Attn: David Glarner
Birch LLC
PO BOX 179173, SAINT LOUIS, MO 63117
Phone: (314) 865-5700
Birch LLC
PO BOX 179173, SAINT LOUIS, MO 63117
Phone: (314) 865-5700
Billing
Attn: David Glarner
Birch LLC
PO BOX 179173, SAINT LOUIS, MO 63117
Phone: (314) 865-5700
Birch LLC
PO BOX 179173, SAINT LOUIS, MO 63117
Phone: (314) 865-5700
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | No | No | The in car lighting shall be operational. Only 2 of 9 bulbs are presently working. | 5/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 6/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The alarm bell shall be operational on auxiliary power. | 6/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.1 Means of Communication (Red Tag) | No | No | The phone recording has the wrong account number and shall be changed to identify the correct account number. | 2/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | The cross head and the pit shall be labeled with the correct elevator number. | 2/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher is expired. | 4/30/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating certificate required in the machine room. | 4/30/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The auxiliary lowering function shall be operational. | 1/24/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The auxiliary lowering function shall be operational. (2nd Notice) | 2/10/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating certificate required in the machine room. | 4/30/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher is expired. | 4/30/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher in the machine room is expired. |