Inspection
Inspection Details
Equipment ID
24466
24466
Inspection Date
3/17/2020
3/17/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Andrew Smith
Andrew Smith
Relief Valve Pressure
0
0
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
0
0
External ID
d286b0a9-5aae-4e09-86f3-ec74b739db5f
d286b0a9-5aae-4e09-86f3-ec74b739db5f
Location
Lake creek United Methodist Church
33074 Lake Creek Rd, Smithton, MO
Phone: (000) 000-0000
33074 Lake Creek Rd, Smithton, MO
Phone: (000) 000-0000
Owner
Attn: UNK
Lake creek United Methodist Church
33074 Lake Creek Rd, Smithton, MO 65350
Phone: (000) 000-0000
Lake creek United Methodist Church
33074 Lake Creek Rd, Smithton, MO 65350
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)7 | Provide pit switch in pit. | 3/17/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Wiring in hoistway must be in approved conduit. | 3/17/2020 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | Accordion doors have split hinges allowing items to pass through during operation without interrupting operation, or opening the gate switch. | 3/17/2020 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)2 | Cartop has water damage that lessens the capability to sustain the required 300 pound minimum load. | 3/17/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | All 3 landing doors our outside of the 3/5 rule with regard to swing type landing doors. | 3/17/2020 | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Main hoisting cables badly rouged and worn. Replace. | 3/17/2020 | |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)2 | Car frame bent out of place. | 3/17/2020 | ||
| MO Minimum : Elevators | (N) - Guide Rails | (N)1 | Car stabilizer rail bracket loose on cartop. | 3/17/2020 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency light and bell not working | 3/4/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | MCP needed | 3/14/2026 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Hoistway door to sill clearance over 3/4 in. | 4/18/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | MCP needed | 3/14/2026 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Hoistway door to sill clearance over 3/4 inch. | 3/12/2025 |