Inspection
Inspection Details
Equipment ID
1531
1531
Inspection Date
7/7/2020
7/7/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Christopher Wiseman
Christopher Wiseman
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
29
29
External ID
21fb752d-eb34-41af-a0d4-f6dee023695e
21fb752d-eb34-41af-a0d4-f6dee023695e
Location
One Park Center
2025 W SUNSHINE ST, SPRINGFIELD, MO
Phone: (417) 863-8880
2025 W SUNSHINE ST, SPRINGFIELD, MO
Phone: (417) 863-8880
Owner
Attn: National Avenue Office Park
Eoff & Associates
2025 W SUNSHINE ST STE 132, SPRINGFIELD, MO 65807-2219
Eoff & Associates
2025 W SUNSHINE ST STE 132, SPRINGFIELD, MO 65807-2219
Billing
Attn: Eoff & Associates
2025 W SUNSHINE ST STE 132, SPRINGFIELD, MO 65807-2219
2025 W SUNSHINE ST STE 132, SPRINGFIELD, MO 65807-2219
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 4/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Have the fire exinguisher re-certified | 4/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Clean the machine room | 12/21/2022 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 8.6.4.7 Cleaning of Hoistways | No | No | Clean down the hoistway top to bottom | 4/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | Replace the burnt-out ceiling light tubes as 2 are required. | 4/28/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 4/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Have the expired fire extinguisher re-certified | 4/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.6.11.3 Cleaning of a Car and Hoistway Transparent Enclosure | No | No | Provide a written program for cleaning the hoistway glass panels, in the machine room. | 4/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a written Maintenance Control Program (MCP) in the machine room. | 4/28/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 6/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replace the emergency phone as it will not dial out | 8/13/2025 |