Inspection
Inspection Details
Equipment ID
24226
24226
Inspection Date
6/23/2020
6/23/2020
Inspection Type
New Installation
New Installation
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
James Dalton
James Dalton
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
a2ee3524-4929-4714-914a-be933a71cfe4
a2ee3524-4929-4714-914a-be933a71cfe4
Location
Holiday Inn Express
50 Richmond Center Blvd, St. Peters, MO
Phone: (000) 000-0000
50 Richmond Center Blvd, St. Peters, MO
Phone: (000) 000-0000
Owner
Attn: UNK
OHM Group
10812 Saint Charles Rock Road, St. Ann, MO 63074
Phone: (314) 209-9200
OHM Group
10812 Saint Charles Rock Road, St. Ann, MO 63074
Phone: (314) 209-9200
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.26.2.7 | x | Stop switch not located adjacent to pit access ladder | 7/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 3.18.3.3 | x | Negative jack clearence. Car bottoms out on jacks 2 inches be fore buffers bottom out | 7/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Seal hoistway penetrations | 7/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Provide dedicated phone line for emergency phone | 7/31/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | x | Ceiling has 2 deep pockets one has sprinklerhead and heat the other does not leaving half the machine room unprotected | 7/31/2020 | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/11/2022 | ||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 1/5/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | The auxiliary power lowering operation shall be functional. | 6/28/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/11/2023 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | x | The auxiliary power lowering operation shall be functional. (2nd Notice) | 9/19/2023 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Oil shall be cleaned from pit and the source of the leak shall be corrected. | 9/19/2023 |