Inspection
Inspection Details
Equipment ID
1258
1258
Inspection Date
6/8/2020
6/8/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
de8b9800-6fe4-4d14-87a6-df2b65b02483
de8b9800-6fe4-4d14-87a6-df2b65b02483
Location
O'Fallon City Hall
100 N MAIN ST, O FALLON, MO
Phone: (314) 574-1806
100 N MAIN ST, O FALLON, MO
Phone: (314) 574-1806
Owner
City of O'Fallon
100 N MAIN ST, O FALLON, MO 63366-2200
100 N MAIN ST, O FALLON, MO 63366-2200
Billing
Attn: City of O'Fallon
100 N MAIN ST, O FALLON, MO 63366-2200
100 N MAIN ST, O FALLON, MO 63366-2200
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room shall have a current test tag. | 10/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.1.7.5 - Emergency lowering shall be operational. | 10/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room shall have a current test tag. | 1/16/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Emergency lowering shall be operational. | 1/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room shall have a current test tag. The tag is expired. (2nd Notice) | 1/16/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency lowering shall be operational. (2nd Notice) | 4/3/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/16/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency lowering shall be operational. (2nd Notice) Note: This has been reported as a deficiency for the last several years. When operating on emergency lowering, the elevator is trying to run up (pump motor contactor is energized) which is isn't able to do, and also isn't designed to do. It appears this may be a problem introduced when the emergency lowering unit was added to this elevator. | 1/17/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/16/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/16/2026 |