Inspection
Inspection Details
Equipment ID
20638
20638
Inspection Date
6/16/2020
6/16/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
05e0ddec-637e-411c-8e7d-86a29bb8cd35
05e0ddec-637e-411c-8e7d-86a29bb8cd35
Location
Mercy Rehabilitation Hospital
14561 N OUTER 40 RD, CHESTERFIELD, MO
Phone: (314) 881-4020
14561 N OUTER 40 RD, CHESTERFIELD, MO
Phone: (314) 881-4020
Owner
Mercy Rehabilitation Hospital
14561 N OUTER 40 RD, CHESTERFIELD, MO 63017-5703
14561 N OUTER 40 RD, CHESTERFIELD, MO 63017-5703
Billing
Attn: Mercy Rehabilitation Hospital
14561 N OUTER 40 RD, CHESTERFIELD, MO 63017-5703
14561 N OUTER 40 RD, CHESTERFIELD, MO 63017-5703
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/9/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 10/25/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | The category 5 test shall be conducted and witnessed on the overspeed valve in 2022. | 5/1/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 1/9/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | A category 5 test shall be performed on the overspeed valve within 90 days. Not currently sealed or tagged. Multi-year violation. | 10/25/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/9/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 1/9/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean. Remove excess debris from pit. | 1/9/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris. | 4/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | OSV shall have current test tag. Tested in 2023, but not tagged. | 4/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Replace piston packing glands. Excessively either recovering pit bucket oil or adding oil, per loss log. | 4/17/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Replace piston packing glands. Excessively either recovering pit bucket oil or adding oil, per loss log. No record of repair in MCP, mechanic recovered 5G of oil from pit bucket in order to perform test. | 4/17/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. No documentation of any kind for 2024 to present. | 4/17/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 4/17/2026 |