|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone does not work.
|
10/13/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.7 - Car door or gate
|
8.11.2.1.1(g)
|
No
|
No
|
Rubber astragal on car gate reversing edge is damaged. Replace same.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Current operating certificate shall be displayed in machine room.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
No
|
No
|
Signage shall be provided in the freight elevator which will read: “THIS IS NOT A PASSENGER ELEVATOR, NO PERSONS OTHER THAN THE OPERATOR AND FREIGHT HANDLERS ARE PERMITTED TO RIDE ON THIS ELEVATOR” and the freight class that the elevator is designed for.The sign shall be located in a conspicuous position and permanently and securely fastened to the car enclosure. The signs shall be durable and readily legible with0.5 in. (13 mm) high letters.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
3.26
|
No
|
No
|
The elevator controller has a large hole in the side from a cooling unit that was installed previously. Seal the large hole to comply with NFPA 70 requirements.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
Yes
|
No
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The elevator car doors failed to open automatically without using the door open button when recalled to the primary landing. Repair and reinspection required in 14 days.
|
11/9/2022
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Place current state operating certificate in elevator machine room
|
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|