Inspection
Inspection Details
Equipment ID
14147
14147
Inspection Date
6/30/2020
6/30/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
a0a05249-d0c3-4f31-85b5-293620d51b48
a0a05249-d0c3-4f31-85b5-293620d51b48
Location
AT & T- Data Center
801 CHESTNUT ST, SAINT LOUIS, MO
Phone: (314) 235-9992
801 CHESTNUT ST, SAINT LOUIS, MO
Phone: (314) 235-9992
Owner
Attn: AT&T Certificate Mgmt
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (314) 606-6816
Email: Gail.Bitondo@LerchBates.com
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (314) 606-6816
Email: Gail.Bitondo@LerchBates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Buffer switch needs to be attached tot the buffer | 6/25/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency light not working on battery backup | 8/19/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Fire service to be tested at a later date. | 8/19/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Alarm bell needs to be sound when stop switch is turned off | 8/19/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Cab emergency light and alarm bell inoperative. | 6/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light inoperative. | 3/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Fire service indicator light is not working, repair same. Re-inspection required | 3/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace missing pushbuttons/covers on both car operating panels | 3/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Reversing edge on north car gate is not working, needs repair. Re-inspection required | 3/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing push buttons/cover in both operating panels. | 3/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | In car fire service light does not work. Repair same. Reinspection required within 90 days. | 4/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance Control Program records need to be up to date, including monthly fire service checks. | 3/18/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 3/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Buzzer on cartop North Side has exposed wiring. Provide proper conduit/cover to enclose wiring. | 3/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide signage in car in conspicuous place stating: FREIGHT ELEVATOR NO PASSENGERS, and proper class loading. All signage to be at least 1/2" tall | 3/18/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication does not work. Repair same. reinspection required within 90 days. | 4/20/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are at minimum diameter and need to be shortened. Replace same within 90 days. | 4/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned. | 3/18/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of current of state certificate of operation needs to be properly displayed in machine room. | 3/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Reversing edge on North care gate is not working. Repair same. | 4/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing pushbuttons / covers in both panels | 3/18/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | In car fire service light does not work, needs repaired. Re-inspection required within 90 days | 4/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Buzzer on car top north side has exposed wiring. Provide proper conduit / cover to enclose wiring. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide signage in car in conspicuous place stating "FREIGHT ELEVATOR NO PASSENGERS" and proper class loading. All signage to be at least 1/2" tall | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are at a minimum diameter and need to be shortened, replace the same within 90 days. Re-inspection required | 4/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Reversing edge on north car gate is not working, needs repaired. Re-inspection required | 4/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Buffer switch has fallen off of the buffer and is laying on the pit floor | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace missing pushbuttons / covers in both operating panels | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | In car fire service light does not work, repair same. Re-inspection required | 1/7/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Buzzer on cartop North side has exposed wiring. Provide proper conduit / cover to enclose wiring. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide signage in car in conspicuous place stating: FREIGHT ELEVATOR NO PASSENGERS and proper class loading. All signage to be at least 1/2" tall. | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are at a minimum diameter and need to be shortened. Replace same within 90 days. Re-inspection required | 1/7/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diameter and are stretched (0" of counterweight runby) and need to be replaced. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light inoperative. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | In car fire service light does not work, repair same. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace missing pushbuttons / covers in both operating panels | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Buzzer on cartop North side has exposed wiring. Provide proper conduit / cover to enclose wiring. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide signage in car in conspicuous place stating "FREIGHT ELEVATOR NO PASSENGERS" and proper class loading. All signage to be at least 1/2" tall | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Buffer switch has fallen off of the buffer and is laying on the pit floor |