Inspection
Inspection Details
Equipment ID
14945
14945
Inspection Date
7/17/2020
7/17/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Scott Tiemann
Scott Tiemann
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
12
12
External ID
2419de0d-de36-4c89-9941-ec8bf2016528
2419de0d-de36-4c89-9941-ec8bf2016528
Location
Westfield Shoppingtown-South County
18 S COUNTY CENTER WAY, SAINT LOUIS, MO
Phone: (314) 892-5203
18 S COUNTY CENTER WAY, SAINT LOUIS, MO
Phone: (314) 892-5203
Owner
Attn: CBL & Associates Properties Inc
CBL & Associates Properties Inc
PO Box 209218, Austin, TX 78720
Phone: (423) 490-8843
CBL & Associates Properties Inc
PO Box 209218, Austin, TX 78720
Phone: (423) 490-8843
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a written maintenance control program on site including documents listed in section 8.6.1.2.2 | 10/1/2025 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | Overspeed valve is not sealed and must have a category 5 test performed within 90 days or less | 10/5/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Cab floor very worn. Repair/replace as needed. | 10/1/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Not working correctly. | 3/8/2022 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Back cab wall damaged, repair as needed. | 10/1/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Cab back wall missing hand rail, replace. | 10/1/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Expired. | 10/1/2025 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | Cab floor very worn, repair/replace as needed | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor cable is broken, needs repaired. Re-inspection required | 8/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car was not answered when tested. Provide for phone to be answered 24/7 by personnel authorized to take appropriate actions. Re-inspection required | 8/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor cable is broken, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car was not answered when tested. Provide for phone to be answered 24/7 by personnel authorized to take appropriate actions. Re-inspection required | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Failed Cat 5 inspection, completed the annual portion only. Re-inspection required |